418 MHz Receiver
The Point Six 418 MHz unit receives the RF signal from one or more wireless temperature or humidity transmitters which have a range of 100 feet. The receiver then outputs the values to any Analog Output Module through an RS485 four-wire bus.
|

|

|
418 MHz to 900 MHz Repeater
The Point Six Repeater receives the 418 MHz RF signal from one or more wireless temperature or humidity transmitters which have a range of 100 feet. The Repeater re-transmits the signal at 900 MHz to a distance of 1000 feet to a BAPI 900 MHz Receiver.
|

|

|
900 MHz Receiver
The Point Six 900 MHz unit receives a repeated or re-transmitted RF signal from one or more wireless temperature or humidity transmitters. The transmitter signal (418 MHz) is received by a Point Six Repeater and then re-transmitted at 900 MHz up to a 1000 feet to the 900 MHz Receiver.
|

|

|
Current Output Module (COM)
The Current Output Module (COM) converts the data from the Wireless Receiver into a linear 4-20 mA signal for the DDC controller.
|

|

|
Resistance Output Module (ROM)
The Resistance Output Module (ROM) converts the data from the Wireless Receiver into a Resistance for the DDC controller. The unit is factory calibrated to output a 10K-2 or 10K-3 thermistor curve.
|

|

|
Relay Output Module (RYOM)
The Relay Output Module (RYOM) converts the data from the Wireless Receiver into a floating switch closure for the DDC controller. It is typically trained to the occupant override button on the side of the BAPI wireless temperature and/or humidity transmitter.
|

|

|
Voltage Output Module (VOM)
The Voltage Output Module (VOM) converts the data from the Wireless Receiver into a linear 0-5 volt or 0-10 volt signal for the DDC controller.
|

|